Opening working days:
08:00AM to 17:00PM
New Zealand time
(or when I’m online is visible)
No-Break DC UPS
No-Break™DC UPSsystems are truly unique.
Click on the appropriate the
image below for a 6 minute Demonstration of the
No-Break™DC UPS System to find out more.
High Res
(21 MB) Low Res (7 MB)
No-Break™DC
UPSsystems maximises the
integrity of standby battery installations whilst optimising the life and
availability of the back up batteries. You always have DC power when you need it.
The system is the ideal
solution for:
Critical systems from 100W to 750W and
above using parallel operation
Applications having standing load with back up
standby battery installed
Systems which require no transition from mains
to battery backup
Providing cost effective management of your
battery system investment
Lower power systems that require battery testing (see battery condition test below)
Battery Condition Test Function (BCT)
(Extra Functionality of the No-Break™ DC Range and not integrated with standard models)
Overview
Considerations
A battery consists of a series of 2V
cells (a battery of cells, hence its name). A 12V battery will have 6 of these
cells in series. Sometimes, one of the cells will “break”, something commonly
referred to as “the battery has dropped a cell”. This will have all sorts of
repercussions, including causing a battery charger to overcharge the remaining
cells (and boiling it dry), and/or producing a much lower output voltage which
can cause physical damage to the load.
1. The BCT
function ( if enabled) reduces the voltage of the power supply and
allows the battery to power the load. During the BCT an additionalrelay changes state to indicate that the BCT is in progress. This
relay may be used to add additional load current to provide a quicker and/or
more meaningful test for the battery (see para. 7 below).
A battery condition
test tries to detect these “breakages”. Effectively, it raises red flags so
that the operators of the battery have a warning (“replace this battery!”)
before they have to rely on it due to a mains failure. Certain reliability
critical applications (e.g., fire alarms) have standards that insist on a
certain level of battery condition testing. The fire safety standards, for
example, specify that a battery conditions test be done for 1 hour every 24
hours for all battery banks.
2. If the
system detects that the battery terminal voltage has fallen below a set value
the BATT SYS OK alarm will
be activated and the Battery System alarm LED on the front panel will flash to
indicate a fault condition. This battery ‘ok / failure’ threshold is usually
set to 2.033V/cell (i.e. 48.8V for a 48V nominal system) but can be adjusted to
suit the specific battery types and installation requirements. Once a battery
failure condition is detected the power supply unit will immediately abort the
test and revert to mains input power. The Battery System alarm LED will
continue to flash and the BATT SYS
OK alarm will stay latched (de-energized state) until either both the
mains power input and the battery are disconnected briefly or the system
passes the next BCT successfully.
The BCT is an additional feature of the No-Break TMDC system that supports the
user with determining the condition of the back-up batteries. It will
provide an early warning for batteries showing age related problems.
Please read the considerations in the next column or download the additional notes below.
3. The
frequency and the duration of the BCT may be specified by the customer.
The requested times will be set during the manufacturing process and cannot be
altered later. See para. 8 below for a typical recommended setting.
4. The
SR250/500/750 series also allow a manual start of a BCT by pushing the BATT
SYS OK pushbutton on the front
panel.
for No-Break™DC UPSextra notes for the battery
condition test and over-current protection circuit.
5. To prevent
a BCT with partially discharged batteries a mains-fail can reset the internal
BCT interval timer. The criteria for resetting the interval timer is that a
mains-fail exceeds a specified time (i.e.5min) and that there are less then 2
days to the next scheduled BCT. The resetting of the interval timer
delays the BCT by the interval time.
for SR100iNo-Break™DC UPS important configuration notes
for the battery condition test
6.
To improve the reliability of the BCT results, we recommend that sufficient
load be applied to the battery during the test. If any additional loading is
not applied directly to the battery connection but via the system then there is
an upper limit of this loading. The Innovative
Energies No-Break TMDC system has a built-in electronic
over-current protection in the battery circuit. This limit allows the battery
to supply up to 1.5 times the rated current of the power supply unit
continuously. If the battery current exceeds this value the electronic circuit
breaker (ELCB) will open and disconnect the battery from the load.
for SR250 / 500 / 750C No-Break™DC UPS important configuration
notes for the battery condition test
7.
A BCT performed at 2 monthly intervals with a
battery loaded at C20/4 amps applied for 10minutes would provide
some good indication. For a battery rated at a C20 = 100Ah the total
load during the test should be 25A.
for Complete No-Break™DC UPSoverview including state
diagrams and LED alarm conditions.
8.
Care must be taken that the cabling to the battery
is of adequate capacity to minimize voltage drops which are a cause of false
alarms (battery reported as fail while still ok) when using the BCT function.
I.e with the a 25A current and a 2m cable of 6mm2 to the Battery a drop
of ~300mV should be expected. It might be necessary to use separate wiring for
additional battery loading.
Rack mount option with optional V/I meter
9.
In situations where the system load current fluctuates significantly the result
of a BCT can become meaningless as the rate of discharge is unknown. Only
additional (constant) loading to the battery during the BCT can improve this
situation.
No- Break
DC UPS - Series C
10.
The Innovative Energies No-Break
TMDC system is available with a ‘T’ option for temperature
compensated battery charging. The battery ‘ok / failure’
threshold is not temperature compensated and the temperature dependency of the
battery terminal voltage and capacity during a BCT needs to be taken into
account.
No- BreakDC
UPS - Seriesi(comms)
11.
The BCT should be used in conjunction with other maintenance checks in
determining whether the battery system will operate in the event of a power
failure. It should not be relied on as a definitive test as every
battery has slightly different design and hence operating characteristics.